ExEco gas burners

Modulating gas burners ExEco RS 310-810/M BLU

High-power BLU series with mechanical control and reduced nitrogen oxide emissions. The reduction is achieved by the gorenje head design and precise control, without loss of flame power and stability. Five standard sizes from 400 to 8010 kW.

Modulating gas burners ExEco RS 310-810/M BLU
Specifications
ManufacturerExEco
SeriesRS 310-810/M BLU
Burner typeMonoblock, Modulation, Low NOx
Heat output400-8010 kW
Fuel typeNatural gas; LPG (after conversion)
Control typeModulating with mechanical control: cam with variable profile, servo drive and thrust. For modulation, you need a sensor and a PID controller.
Power supply400 V, 50 Hz, three-phase
Control systemMicroprocessor control and safety unit with fault diagnostics
Flame monitoringIonisation probe, electrode ignition
Combustion headStainless steel blast tube, flame stability disc
Emission classClass 2 to GOST EN 676-2016 — NOx ≤ 120 mg/kWh
ConnectionFlanged, with heat shield and fixing kit
Scope of supplyBurner, gas train adapter, gasket, heat shield, fixings, data sheet and manual
Standards RussiaГОСТ R 50591-2013 — concentration limits NOx
Models and part numbers
ModelHeat output, kWPart number
RS 310/M BLU400/1200÷3630BU090011
RS 410/M BLU500/1500÷4450BU090020
RS 510/M BLU680/1800÷5250BU090031
RS 610/M BLU1000/2200÷6250BU090041
RS 810/M BLU1200/3500÷8010BU090050
Design
Questions

Frequently asked questions

What is the power of the burners ExEco RS 310-810/M BLU?
The thermal power range of the series is 400-8010 kW.
What type of regulation does ExEco RS310-810/M BLU have?
Modulating with mechanical control: cam with variable profile, servo drive and thrust. For modulation, you need a sensor and a PID controller.
What kind of gas do ExEco RS 310-810/M BLU burners use?
As standard, on natural gas. Most models can be converted to LPG (propane-butane) with a conversion kit; the work must be carried out by a certified engineer.
Is the ExEco RS 310-810/M BLU suitable for a boiler from another manufacturer?
Yes. The burners are universal and mount on boilers of both Russian and foreign makes. What matters is selecting the correct size and combustion head length for the specific boiler.
What should I state when ordering?
Boiler output, gas type and mains pressure, control and emission requirements, and the distance from the flange to the furnace. If you do not have the parameters, send the boiler model and we will make the selection.
What are the delivery times?
Fast-moving sizes ship from stock, the rest is made to order. The exact lead time and price are confirmed in the quotation. Delivery across Russia and the CIS.
When to take /M BLU, and when / E BLU?
/M — mechanical control, simpler and cheaper, suitable for an autonomous boiler room. /E is an electronic gorenje manager with digital interfaces, which is needed for integration into automated process control systems and with increased accuracy requirements.

We will select a burner for your boiler

State the boiler output, fuel type and pressure, and the control and emission requirements — we will select the model and prepare an offer with price and lead time.

Request a quote