ExEco gas burners

Modulating gas burners ExEco GAS P/M 9-10

A series with an extended modulation range and adaption to work with different gases. Two standard sizes cover the range of 870-4885 kW — large hot water and steam boilers, process installations.

Modulating gas burners ExEco GAS P/M 9-10
Specifications
ManufacturerExEco
SeriesGAS 9 P/M – 10 P/M
Burner typeMonoblock, modulating
Heat output870-4885 kW
Fuel typeNatural gas; LPG (after conversion)
Control typeModulating with mechanical control: cam with variable profile, servo drive and thrust. For modulation, you need a sensor and a PID controller.
Power supply400 V, 50 Hz, three-phase
Control systemMicroprocessor control and safety unit with fault diagnostics
Flame monitoringIonisation probe, electrode ignition
Combustion headStainless steel blast tube, flame stability disc
Emission classClass 2 to GOST EN 676-2016 — NOx ≤ 120 mg/kWh
ConnectionFlanged, with heat shield and fixing kit
Scope of supplyBurner, gas train adapter, gasket, heat shield, fixings, data sheet and manual
Models and part numbers
ModelHeat output, kWPart number
GAS 9 P/M870/1744÷3488BU080010
GAS 10 P/M1140/2441÷4885BU080020
Design
Questions

Frequently asked questions

What is the capacity of ExEco GAS P/M burners?
The thermal power range of the series is 870-4885 kW.
What type of regulation does ExEco GAS P/M have?
Modulating with mechanical control: cam with variable profile, servo drive and thrust. For modulation, you need a sensor and a PID controller.
What kind of gas do ExEco GAS P/M burners run on?
As standard, on natural gas. Most models can be converted to LPG (propane-butane) with a conversion kit; the work must be carried out by a certified engineer.
Is ExEco GAS P/M suitable for a boiler from another manufacturer?
Yes. The burners are universal and mount on boilers of both Russian and foreign makes. What matters is selecting the correct size and combustion head length for the specific boiler.
What should I state when ordering?
Boiler output, gas type and mains pressure, control and emission requirements, and the distance from the flange to the furnace. If you do not have the parameters, send the boiler model and we will make the selection.
What are the delivery times?
Fast-moving sizes ship from stock, the rest is made to order. The exact lead time and price are confirmed in the quotation. Delivery across Russia and the CIS.
How does the GAS P/M differ from the RS series of comparable power?
An extended range of modulation and adaptation to work with different gases. If the composition of the gas differs from the usual natural gas, this series is preferable.

We will select a burner for your boiler

State the boiler output, fuel type and pressure, and the control and emission requirements — we will select the model and prepare an offer with price and lead time.