Wires and lightning protection cables are maintained at the required level between the anchor sections. The most widespread type of supports: there are more of them on straight sections of the highway than all the others combined.

| Type of support | Intermediate |
| Designation | P, PS |
| Voltage classes | 35 kV · 110 kV · 220 kV · 330 kV · 400 kV · 500 kV · 750 kV |
| Design | Lattice, from plate and angle sections |
| Material | Steel 09G2S-12 / S345-3 or St3ps5 / S245, S255 |
| Corrosion protection | Hot-dip galvanising to GOST 9.307-21 |
| Service life | At least 50–70 years without repainting |
| Manufacturing | To standard type designs or to the customer's structural drawings |
| Scope of supply | Shipping sections and fasteners; pile caps and embedded parts on request |
| Documents | Data sheet, steel certificates and corrosion protection documentation |
The tower weight and dimensions are confirmed when the detail drawings are issued for the wind and ice region of the site.
The intermediate support is not designed for the high weight of the wires: it accepts the vertical load from their weight, ice and wind pressure, but not the one-sided tension. Due to this, the construction is lighter and cheaper than an anchor-angle one, and on a long track this is a decisive cost factor.
They are indicated by the letters P and PS, followed by the voltage class. The PS is an intermediate free—standing one. The letter "T" in the stamp indicates a rope with two cables, the number after the hyphen shows the number of chains: odd — single chain, even — double chain.
We manufacture according to standardized standard designs for the voltage class and according to the customer's drawings КМ. Anticorrosive protection is hot—dip galvanizing according to ГОСТ 9.307-21, the service life of the structure is at least 50-70 years.
We receive the schedule, questionnaire or structural drawings.
We select the types for the route and climatic region and calculate the cost.
We issue working drawings and manufacture the structures with hot-dip galvanising.
Shipped as sections by road or rail.
The intermediate one only accepts the weight of the wires and the wind load, while the anchor one also accepts full one—sided gravity. Therefore, the anchor line is heavier and more expensive, and the intermediate one is placed where the highway runs straight. You can't replace one with the other: these are different calculation schemes.
It depends on the stress class, terrain, and estimated span. These are usually several supports per kilometer, and the exact number is taken from the route design. To calculate the delivery, it is enough to send a list of supports from the project.
A wire rope with two lightning protection cables. The letter "P" in the stamp means the transfer of the wires of the tier to the middle one, the "+" sign indicates the height of the prefix to the base support.
Yes. We work according to standard designs and drawings КМ of the customer. In the second case, we produce working drawings КМД and produce according to them.
Send the tower schedule or the route parameters — we will select the types and prepare a calculation.