Emergency relief of excess pressure from a vertical reservoir when the capacity of the breathing valves is insufficient. It is installed additionally to them, on the roof mounting pipe.

The emergency valve releases excess pressure into the atmosphere, which occurs when the gas space is intensively heated — from a fire in an adjacent tank, boiling of the product or its explosion. It is installed in addition to the breathing valves and comes into operation when their capacity is obviously low. This avoids the deformation and destruction of the tank.
The plate rests on the neck of the housing, the sealed plate-neck connection eliminates losses from evaporation in the normal mode. The contact surfaces of the plate and seat are covered with a fluoroplastic film — the valve does not freeze. When triggered, the alarm shoots up and locks in the upper position: the staff sees the fact of the reset from afar. After the pressure drops, the valve closes itself, and the alarm is manually returned to the operating position.
| Type | Emergency valve, non-freezing |
|---|---|
| Purpose | Emergency relief of excess pressure from vertical cylindrical tanks |
| Applicability | RVS with oil and petroleum products with a volume of 1000-50000 m3 |
| Tank operating limits | Overpressure not more than 2.0 kPa, vacuum not more than 0.25 kPa |
| Frost protection | Fluoroplastic coating of plates and saddles |
| Alarm operation | Extendable alarm, manual return |
| Material performance | Carbon steel, aluminum alloy, stainless steel on request |
| Climatic version | Y, XL, UHL, placement category 1 for ГОСТ 15150-69 |
| Parameter | Meaning |
|---|---|
| Conditional passage DN, mm | 500 |
| Actuation pressure | 2350-2550 Pa (235-255 mm of water) |
| Throughput capacity, m3/h, max | 30000 |
| Overall diameter, mm, max. | 1020 |
| Height in the working position, mm, max. | 693 |
| Height after actuation, mm, max. | 858 |
| Connection dimensions, mm | D 640, D1 600, d 22, n 16 rel. |
| Weight, kg, max | 140 |
It is installed on the mounting pipe on the tank roof.
State the size and parameters, or send a specification — we will make the selection and prepare a quotation.
Request a quoteLeave your contact details — we will select the model and prepare a quotation. We reply within one working day.