Breather valves

Emergency valve КА-500

Emergency relief of excess pressure from a vertical reservoir when the capacity of the breathing valves is insufficient. It is installed additionally to them, on the roof mounting pipe.

Emergency valve КА-500
Description

Purpose and design

The emergency valve releases excess pressure into the atmosphere, which occurs when the gas space is intensively heated — from a fire in an adjacent tank, boiling of the product or its explosion. It is installed in addition to the breathing valves and comes into operation when their capacity is obviously low. This avoids the deformation and destruction of the tank.

The plate rests on the neck of the housing, the sealed plate-neck connection eliminates losses from evaporation in the normal mode. The contact surfaces of the plate and seat are covered with a fluoroplastic film — the valve does not freeze. When triggered, the alarm shoots up and locks in the upper position: the staff sees the fact of the reset from afar. After the pressure drops, the valve closes itself, and the alarm is manually returned to the operating position.

Parameters

Technical specifications

TypeEmergency valve, non-freezing
PurposeEmergency relief of excess pressure from vertical cylindrical tanks
ApplicabilityRVS with oil and petroleum products with a volume of 1000-50000 m3
Tank operating limitsOverpressure not more than 2.0 kPa, vacuum not more than 0.25 kPa
Frost protectionFluoroplastic coating of plates and saddles
Alarm operationExtendable alarm, manual return
Material performanceCarbon steel, aluminum alloy, stainless steel on request
Climatic versionY, XL, UHL, placement category 1 for ГОСТ 15150-69
Models

Technical parameters

ParameterMeaning
Conditional passage DN, mm500
Actuation pressure2350-2550 Pa (235-255 mm of water)
Throughput capacity, m3/h, max30000
Overall diameter, mm, max.1020
Height in the working position, mm, max.693
Height after actuation, mm, max.858
Connection dimensions, mmD 640, D1 600, d 22, n 16 rel.
Weight, kg, max140

It is installed on the mounting pipe on the tank roof.

Questions

Frequently asked questions

How does an emergency valve differ from a breathing valve and why do we need both?
The breathing valve works constantly and keeps the pressure within the operating limits. The emergency door has been silent for months and opens only when there is not enough breathing equipment — in case of a fire nearby or equipment failure. One does not replace the other.
When is one КА-500 per tank not enough?
The number of emergency valves is calculated according to the required capacity for a specific volume and conditions. Send the tank parameters and we'll calculate them.
What should I do after the valve is triggered?
The valve closes itself as soon as the pressure drops below the actuation pressure. The alarm remains in the emergency position until it is manually returned — this is done on purpose so that the reset does not go unnoticed.
Which material execution should I choose?
Carbon steel is the basic option, aluminum alloy is lighter and is used where mass on the roof is important. The stainless version is manufactured on demand for a specific environment.

Do you need an emergency valve КА-500?

State the size and parameters, or send a specification — we will make the selection and prepare a quotation.

Request a quote